产品阐述 |
Input 0/4 mA ... 20 mA
Output 0/4 mA ... 20 mA |
General specifications |
Signal type | Analog input |
Supply |
Connection | Power Rail or terminals 14+, 15- |
Rated voltage | 20 ... 35 V DC |
Ripple | within the supply tolerance |
Power loss | 1.8 W |
Power consumption | max. 2.7 W |
Input |
Connection | terminals 1+, 3-; 4+, 6- |
Input signal | 0/4 ... 20 mA |
Available voltage | ≥ 16 V at 20 mA, terminals 1+, 3 |
Output |
Connection | terminals 7-, 8+; 10-, 11+ |
Load | 0 ... 550 Ω |
Output signal | 4 ... 20 mA (overload > 25 mA) |
Ripple | max. 50 µA rms |
Transfer characteristics |
Deviation | at 20 °C (68 °F), 0/4 ... 20 mA
≤ 10 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage |
Frequency range | input to output: bandwidth with 1 Vpp signal 0 ... 7.5 kHz (-3 dB)
output to input: bandwidth with 1 Vpp signal 0.3 ... 7.5 kHz (-3 dB) |
Rise time | 20 µs |
Start-up time | 200 µs |
De-energized delay | 20 µs |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2004/108/EC | EN 61326-1:2006 |
Conformity |
Electromagnetic compatibility | NE 21:2006 |
Protection degree | IEC 60529:2001 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Protection degree | IP20 |
Mass | approx. 150 g |
Dimensions | 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 in) , housing type B2 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |