Power supply | 24 V DC ±10%, filtered and regulated |
Power consumption | approx. 2 W (without valve - without sensor input) |
Input | | |
Setpoint | | |
Standard 4-20 mA | Sourcing mode |
| Max. input impedance: 70 W |
| Resolution: 5.5 mA |
Standard 0-10 V | Max. input impedance: 11.5 kW |
| Resolution: 2.5 mV |
Sensors | | |
Standard 4-20 mA | Sourcing mode |
| Max. input impedance: 70 W |
| Resolution: 5.5 mA |
Standard 0-10 V | Max. input impedance: 11.5 kW |
| Resolution: 2.5 mV |
Frequency | | |
Input 1 | External sensor |
| min. 0.25 Hz / max. 1 kHz |
| input impedance: >1 kW |
| Signal type: Sinus, square, triangle pulse (> 3000 mVpp, |
| max. 30 Vpp) |
Input 2 | Internal Hall sensor |
| min. 0.25 Hz / max. 1 kHz |
| (only with Bürkert Type S030 flow fitting) |
Pt100 (2 wires) | Measuring range: 0°C...200°C |
| |
| Measuring current: 1 mA |
| Measuring error: <0.5°C |
Sensor power supply | 24 V DC, max. 1 A |
Binary input | Input impedance: 10 kW |
| |
| Operating threshold: 3 V-30 V |
| Max. frequency: 1 kHz |
Outputs | | |
Continuous signal | Standard signal 4-20 mA |
| max. loop resistance: 680 W |
| accuracy: 0.5% |
| Standard signal 0-10 V |
| max. current: 20 mA |
| accuracy: 0.5% |
Discontinuous signal | 2 transistor outputs for PWM*) or PTM*) signal |
| Control frequency 1.2 kHz-20 Hz |
| resolution max.: 16 Bit (depend from frequency) |
| max. current load: 1.5 A |
| switching voltage: 24 V DC |
Binary output | Transistor output (PNP) (configurable) |
| max. current load: 1.5 A |
| switching voltage: 24 V DC |
Total load of all outputs | max. 1.5 A |
Controller modes | PI-Control, 2 point and 3 point, cascaded |
| Up to 2 Binary out with windows and hysteresis mode |