测量原理 | Vibration Liquids |
Characteristic / Application | Modular housing concept High process temperatures up to 280°C wide range of process connections Analogue and bus interfaces Extensive certificate range (e.g. Ex,WHG) compact, e.g. pipes Dual Sealing / Second line of defense |
Supply / Communication | PROFIBUS PA 19...253V AC 10...55V DC-PNP 19...253V AC bzw 10...55V DC 8/16mA, 11...36V DC NAMUR PFM |
Ambient temperature | -50 °C...+70 °C (-58 °F...+158 °F) |
Process temperature | -60 °C...+280 °C (-76 °F...+540 °F, (300°C / 572 °F 50h, cumulated |
Process pressure absolute / max. overpressure limit | Vacuum...100 bar (Vacuum...1450 psi) |
Main wetted parts | 316L / Alloy PFA and Enamel on request |
Process connection | Thread: G3/4A, G1A, R3/4", R1, NPT3/4, NPT1 Flange: DIN DN25...DN100, ASME 1"...4", JIS 2...100A |
Sensor length | 65mm (2.56") |
Output | PROFIBUS PA 19...253V AC 10...55V DC-PNP 19...253V AC bzw 10...55V DC 8/16mA, 11...36V DC NAMUR PFM |
Certificates / Approvals | ATEX, FM, CSA, TIIS Overfill prevention WHG SIL EN10204-3.1 NACE Marine GL/ABS ASME B31.3 |
Options | Heavy duty stainless steel housing mainly for the oil and gas industry |
Specialities | Foamdetection Detect a densitychange second line of defense |
Components | FTL325P/FTL375P Interface PFM FTL325N/FTL375N Interface NAMUR |