INPUT |
---|
Phase |
1Ø |
---|
Voltage |
110 / 220Vac±10% | 220Vac±10% |
---|
Frequency |
50 / 60 Hz |
---|
Max. Current |
10A / | 20A / 10A | 20A | 30A | 50A |
---|
Power Factor |
0.7 |
---|
AC OUTPUT |
---|
Max. Power |
500VA | 1000VA | 2000VA | 3000VA | 5000VA |
---|
Max. Current (r.m.s)*1 |
0-150V | 4.6A | 9.2A | 18.4A | 27.6A | 46.0A |
---|
0-300V | 2.3A | 4.6A | 9.2A | 13.8A | 23.0A |
Phase |
1Ø / 2W |
---|
Total Harmonic Distortion (T.H.D) |
<0.5% at 40 - 100Hz , <1% at 101 - 450Hz (Resistive Load) |
---|
Crest Factor |
≧3 |
---|
Line Regulation |
±0.1V |
---|
Load Regulation |
± (0.5% of output + 0.5V) at Resistive Load |
---|
Response Time |
< 400usec |
---|
SETTINGS |
---|
Voltage |
Range | 0 - 150V / 0 - 300V Selectable |
---|
Resolution | 0.1V |
Accuracy | ±(1% of setting + 2counts) | ±(1% of setting + 5counts) |
Frequency |
Range | 40 - 450Hz Full Range Adjust |
---|
Resolution | 0.1Hz at 40.0 - 99.9Hz, 1Hz at 100 - 450Hz |
Accuracy | ±0.03% of setting |
DC OUTPUT (Option) |
---|
Max. Power |
250W | 500W | 1000W | 1500W | 2500W |
---|
Max. Current |
0-200V | 2.3A | 4.6A | 9.2A | 13.8A | 23.0A |
---|
0-400V | 1.1A | 2.3A | 4.6A | 6.9A | 11. |
SETTINGS |
---|
Voltage |
Range | 0-200V / 0-400V Selectable |
---|
Resolution | 0.1V |
Accuracy | ±(1% of setting + 2counts) |
Ripple and Noise (r.m.s) |
Range | L | < 250mV | < 350mV |
---|
H | < 400mV | < 550mV |
Ripple and Noise (p-p) |
< 2Vp-p | < 3.0Vp-p |
---|
MEASUREMENT |
---|
Voltage (AC & DC) |
Range | 0.0-400.0V |
---|
Resolution | 0.1V |
Accuracy | ± (1% of reading + 2counts) | ± (1% of reading + 5counts) |
Frequency |
Range | 0.0-500.0Hz |
---|
Resolution | 0.1Hz |
Accuracy | ±0.1Hz |
Current (r.m.s)(AC & DC) |
Range | 0.00A - 6.50A | 0.00A - 13.00A | 0.00A - 26.00A | 0.00A - 39.00A | 0.00 - 65.00A |
---|
Resolution | 0.01A |
Accuracy | ± (1% of reading +5counts) |
Power |
Range | 0W - 650W | 0W - 1300W | 0W - 2600W | 0W - 3900W | 0W - 6500W |
---|
Resolution | 1W |
Accuracy | ± (2% of reading +2counts) |
Power Factor |
Range | 0.000-1.000 |
---|
Resolution | 0.001 |
Accuracy | W / VA ,Calculated and displayed to three significant digits |
Opt.628 High Measurement Resolution (For 6905, 6910 & 6920) |
AC OUTPUT |
---|
Current |
Range | L | 0.000A - 0.600A | 0.000A - 1.200A | 0.000A - 2.400A | - | - |
---|
H | 0.50A - 6.00A | 1.00A - 13.00A | 2.00A - 27.00A | - | - |
Resolution | L | 0.001A | - | - |
H | 0.01A | - | - |
Accuracy | ± (1% of reading +5counts) | - | - |
Power |
Range | L | 0.0W - 60.0W | 0.0W - 120.0W | 0.0W - 240.0W | - | - |
---|
H | 50W - 500W | 100W - 1000W | 200W - 2000W | - | - |
Resolution | L | 0.1W | - | - |
H | 1W | - | - |
Accuracy | ± (2% of reading +5counts) | - | - |
DC OUTPUT(Option) |
---|
Current |
Range | L | 0.010A - 0.600A | 0.010A - 1.200A | 0.0010A - 2.400A | - | - |
---|
H | 0.50A - 3.00A | 1.00A - 6.50A | 2.00A - 13.50A | - | - |
Resolution | L | 0.001A | - | - |
H | 0.01A | - | - |
Accuracy | ± (1% of reading +5counts) | - | - |
Power |
Range | L | 0.0W - 60.0W | 0.0W - 120.0W | 0.0W - 240.0W | - | - |
---|
H | 50W - 250W | 100W - 500W | 200W - 1000W | - | - |
Resolution | L | 0.1W | - | - |
H | 1W | - | - |
Accuracy | ± (2% of reading +5counts) | - | - |
GENERAL |
---|
Memory |
3 memories (M1, M2, M3) |
---|
Efficiency |
≧80%(at Full Load ) |
---|
Protection |
Over Current, Short Circuit, Over Temperature, Over Voltage, Over Power, and Alarm |
---|
Calibration |
Front Panel Calibration |
---|
Operation Environment |
0 - 40℃ / 20 - 80%RH |
---|
Dimension, mm*2 |
W | 430 | 430 | 430 | 430 | 430 |
---|
H | 89 (111.5) | 89 (111.5) | 89 (111.5) | 223 (245.5) | 223 (245.5) |
D | 300 (310) | 400 (410) | 500 (510) | 500 (510) | 500 (510) |
Net Weight |
12.5Kg | 18.2Kg | 30Kg | 57Kg | 65Kg |
---|
*1 At working voltage 110V / 220V | *Product specifications are subject to change without notice. |
*2 Figure in parentheses are maximum values |