MODEL | OUTPUT VOLTAGE | MAX. LOAD | MIN. LOAD | RIPPLE & NOISE | VOLTAGE ACCURACY | LINE REGULATION | LOAD REGULATION | (%) EFF(1). (Typ.) | |
CFM40M033 | 3.3V | 6A | 0A | 50mV | ±1% | ±0.5% | ±1% | 76% | |
CFM40M050 | 5V | 6A | 0A | 1% | ±1% | ±0.5% | ±1% | 80% | |
CFM40M090 | 9V | 4.4 | 0A | 1% | ±1% | ±0.5% | ±1% | 84% | |
CFM40M120 | 12V | 3.34A | 0A | 1% | ±1% | ±0.5% | ±1% | 86% | |
CFM40M150 | 15V | 2.67A | 0A | 1% | ±1% | ±0.5% | ±1% | 87% | |
CFM40M240 | 24V | 1.67A | 0A | 1% | ±1% | ±0.5% | ±1% | 88% | |
CFM40M300 | 30V | 1.33A | 0A | 1% | ±1% | ±0.5% | ±1% | 88% | |
CFM40M360 | 36V | 1.11A | 0A | 1% | ±1% | ±0.5% | ±1% | 88% | |
CFM40M480 | 48V | 0.834A | 0A | 1% | ±1% | ±0.5% | ±1% | 88% | |
Specifications | CFM40M Series Derating Curve | |
INPUT SPECIFICATIONS: |
Voltage …....………........…............................................. 90~264Vac |
Frequency ………………………………………………………..... 47 to 63Hz |
Inrush Current ……………………......................... 60A max. @240Vac |
Input Current ……….………………. 100Vac/1A max., 240Vac/0.5 max. |
Leakage Current …………………………………….….…...…… 100uA max |
OUTPUT SPECIFICATIONS: |
Holdup Time …………………………..……………… 10ms typ. @115Vac |
Short Circuit Protection …………………….…. Hiccup Mode (Auto Recover) |
Over Voltage Protection …………………..…...… TVS Component to Clamp |
Temperature Coefficient ……………………................................. ±0.05%/℃ |
GENERAL SPECIFICATIONS: |
Isolation ……………………..…………………..... Input to output=5,656VDC |
Operating Temperature .............................. 0℃ ~ 50℃(see Derating Curve) |
Storage Temperature ………………..…………....….......…........ -20~85℃℃ |
Humidity .................................................... 93% RH max. Non condensing |
Cooling ………………………..…………………..... Natural Convection |
Switching Frequency …………………………………….……. 65KHz Typical |
MTBF …………… MIL-HDBK-217F, GB, 25℃/115VAC …… 200K hrs min. |
Altitude ……………………..……………………….………..………… 3000m |
Dimensions ………………….… 3.00x2.00x0.91 Inches(76.2*50.8*23.1mm) |
Weight…………………………………………………..…………..… 90g | NOTE: |
SAFETY AND EMC: | 1. Voltage accuracy is set at full load. |
Emission and Immunity …………. EN55011 Class B, FCC CFR 47 Part 18 | 2. Add a 0.1uF ceramic capacitor and a 10uF E.L. capacitor to output for |
EN60601-1-2 , EN61000-3-2 ,EN61000-3-3 | Ripple & Noise measuring @20MHz BW. |
Safety …………………………..…… IEC60601-1, EN60601-1, UL60601-1 | 3. Line regulation is measured from 100Vac to 240Vac with full load. |
4. Load regulation is measured from 10% to full load. |
5. Connectors: AC input: JST VHor equivalent |
DC input: JST VH or equivalent |