QPX1200S直流电源,英国tti QPX1200S的技术说明:
QPX1200S
Bench/System DC Power Supplies, PowerFlex or PowerFlex+ regulated Single Output, 60V/50A1200W Powerflex, No Bus InterfacesBench or System, RS232, USB, GPIB & LAN
Bench or rack mounting with front and rear terminals
Analog interface only (QPX1200S)
Analog, RS232, USB, LAN & GPIB (QPX1200SP)
LAN interface conforms with LXI class C
QPX1200S直流电源,英国tti QPX1200S的产品描述:
Unrivalled Flexibility
The QPX1200 offers users a level of flexibility that can not be achieved with conventional laboratory power supplies.
With a current capability of 20 amps at the maximum output of 60 volts, its PowerFlex design offers increasing output current with reducing output voltage. The QPX1200 can therefore perform the task of many different power supplies.
Example voltage/current combinations include 60V/20A, 48V/2, 37.5V/30A, 26V/40A, and 20V/50A.
High precision
With setting controlled by an instrumentation quality 16 bit DAC, the QPX1200 offers high accuracy and stability.
Local setting can be done using either the numeric keypad or the spin-wheel, and setting resolution is 1mV in up to 60 volts.
Linear output stage for low noise
Mixed mode regulation with a linear output stage gives the QPX1200 exceptionally low output noise for a unit of this power, and ensures fast transient response.
Bench or rack mounting
Unlike most higher power laboratory PSUs, the QPX1200 is equally suited to bench or rack-mount applications.
Output and sense terminals are provided on both the front and rear panels. The case has integral tilt feet, and a 3U rack mount is available as an option.
A wide range of interfaces
The QPX1200S has an analog remote control interface only.
The QPX1200SP has analog, RS-232, USB and LAN (Ethernet) and GPIB interfaces. The LAN interface is fully LXI compliant.QPX1200S直流电源,英国tti QPX1200S的技术参数:
OUTPUT SPECIFICATIONS
Voltage Range:0V to 60V.
Current Range:0A to 50A.
Power Range:Up to 1200W - see PowerFlex power envelope graph.
Operating Mode:Constant voltage or constant current with automatic cross-over and mode indication.
Voltage Setting:By floating point numeric entry or rotary jog wheel; resolution 1mV.
Current Setting:By floating point numeric entry or rotary jog wheel; resolution 10mA.
Setting Accuracy:Voltage - 0.1% +/- 2mV. Current 0.3% +/- 20mA
Setting Stores:Up to 10 set-ups can be saved and recalled via the keyboard or remote interfaces.
Load regulation:<0.01% + 5mV for a 90% load change.
Line regulation:<0.01% + 5mV for a 10% line voltage change.
Ripple & Noise (20MHz bandwidth):Typically <3mV rms, <20mV pk-pk, (Full power).
Transient Response:<250us to within 50mV of set level for 90% load change.
Temp. Coefficient:Typically <100ppm/oC.
Output Protection:Forward protection by OVP trip; maximum voltage 70V. Reverse protection by diode clamp for reverse currents up to 3A.
Protection Functions:
Power Limiter, over-voltage, over-current and temperature trips.
Over Voltage (OVP): Settable 2V to 65V in 0.1V steps
Over Current (OCP): Settable 2A to 5 in 0.1A steps
Over Temperature: Monitors internal temperature rise
Sense Error:Monitors the voltage between the remote sense terminals and output terminals
Status Indication:Display indication of Output On, CV, CI, Power Limit, Over-voltage trip.
Output Switch:Push switch operating electronic power control. LED indication of On state
Output Terminals:Front and rear output and sense terminals. Safety terminals accepting 6mm wire diameter, 6mm plugs or 8mm spades at 50 Amps max, or 4mm plugs at 30 Amps max.
Sensing:Selectable local or remote sensing.
METERING
Display Type:
Large dot-matrix black-on-white backlit LCD. 5 digit voltage meter and 4 digit current meter. Display of limits values, memory contents etc. Wide range of alpha-numeric messages. Limits settings can be displayed simultaneously with measurements.
Meter Resolutions:Voltage: 1mV. Current: 10mA
Meter Accuracies:Voltage: 0.1% of reading +/- 2 digits Current: 0.3% of reading +/- 2 digits
INTERFACES
Analog:Quasi-analog (digitised). Voltage or current, 0 - 5V or 0 - 10V.
Digital:
All digital bus interfaces incorporate full control, readback and status reporting.
Bus Type Selection: From front panel (RS232/USB/LAN).
Setting Resolution:Voltage - 1mV, Current 1mA.
Readback Resolution:Voltage - 10mV, Current 10mA.
USB:Standard USB harware connection.
RS-232:Variable baud rate 9,600 max.
LAN:Conforming to Ethernet standard and LXI-C
GPIB :Conforming with IEEE-488.1 and IEEE-488.2
GENERAL
AC Input:110V to 240V AC +/-10%, 50/60Hz. Installation Category II.
Power Consumption:1600VA max.
Cooling:Intelligent Fan System
Operating Range:+5oC to +40oC, 20% to 80%
RH. Storage Range:-40oC to + 70oC.
Environmental:Indoor use at <2000m, Pollution Degree 1.
Safety:Complies with EN61010-1.
EMC:Complies with EN50081-1 and EN50082-1.
Size:350 x 130 x 413mm (WxHxD) (3U height) . (optional rack mounting kit available).
Weight:9.2kg (20lb). Thurlby Thandar Instruments Ltd. operates a policy of continuous development and reserves the right to alter specifications
without prior notice.