| Items | Specifications | |
| Model | AAP135 | |
Number of input channels | 8, isolated channels | |
| | 2-wire type: Contact ON/OFF, voltage pulse, current pulse | |
Input signal (*3) | (possible to supply transmitter power supply) | |
| | 3-wire type: Power-supply-type voltage pulse | |
Input frequency | 0 to 10 kHz (*4) | |
Withstanding voltage | Between input and system: 500 V AC, For 1 minute | |
Between channels: 500 V AC, For 1 minute (*1) | |
| | |
Minimum input pulse width | 40 μs | |
| | Contact input | |
| | Open/close levels of relay contact and transistor contact | |
| | Open: 100 kΩ or more, Close: 200 Ω or less | |
| | Contact capacity | |
| | When supplying 12 V DC: 15 V DC 15 mA or more | |
Input signal level | When supplying 24 V DC: 30 V DC 30 mA or more | |
| | Voltage/current pulse input (Current input is converted to voltage.) | |
| | VH (high level): 3 to 24 V DC | |
| | VL (low level): -1 to 8 V DC | |
| | VH-VL (swing value): 3 V or more | |
| | Signal source resistance: 1 kΩ or less | |
Shunt resistance | Can be selected from none/200/500/1000 Ω. | |
(Open when power is OFF and for the standby side in a dual-redundant configuration) | |
| | |
Pull-up resistance | 68 kΩ (12 V DC or 24 V DC) | |
Filter | | Filter for eliminating chattering can be set. (*2) | |
Data update period | 2 ms | |
Transmitter power supply | Can select 24 V DC/12 V DC. | |
Limiter value 12 V DC ±10 %: 40 mA, 24 V DC ±10 %: 30 mA | |
| | |
Maximum current consumption | 300 mA (5 V DC), 400 mA (24 V DC) | |
Weight | | 0.3 kg | |
External connection | Pressure clamp terminal, KS cable, MIL connector cable | |
*1: | The withstanding voltage for using MIL connector cable depends on the electrical specifications of its cable. | |
*2: | When the pulse input signal is dry contact (such as from a mechanical relay) up to 10 Hz, it is possible to eliminate the | |
| chattering. | | |
*3: | The connection method of the field devices varies depending on the input signal. | |
| For details, please refer to “Installation Guidance (TI 33Q01J10-01E).” | |
*4: | Input frequency is 0 to 800 Hz to receive no-voltage contact signals between terminal B and C. | |