| Input(执行机构-->主站) | | |
Para | Type | Bit,Value | Mean | Range | |
ReadBack | Float | | 反馈阀位值 | 0-100% | |
WorkState | Byte | 0 | Invalid | | |
1 | Remote SetPointD | | |
2 | Remote SetPoint | | |
3 | Local | | |
4 | Menu Set | | |
5 | Radio SetPointD | | |
6 | Radio SetPoint | | |
7 | DP SetPointD | | |
8 | DP SetPoint | | |
Alarm Info | Byte0 | 0.0 | BATRENEW 电池报警(Battery Low) | 0:No 1:Yes | |
0.1 | BAT_EMPT 电池电量太低(Battery Empty) | 0:No 1:Yes | |
0.2 | TORQUE_O 开向力矩报警(Torque Open Alarm) | 0:No 1:Yes | |
0.3 | TORQUE_C 关向力矩报警(Torque Close Alarm) | 0:No 1:Yes | |
0.4 | TEMP_MOT 电机温度(Motor Temp) | 0:No 1:Yes | |
0.5 | TEMP_ELC 电子温度(Electric Temp) | 0:No 1:Yes | |
0.6 | 24_VOLT 24V(24V) | 0:No 1:Yes | |
0.7 | IN_SIGN 调节信号(Input Signal) | 0:No 1:Yes | |
Byte1 | 0.8 | TORCNT_C 关向力矩次数(Torque Close Num.) | 0:No 1:Yes | |
1.1 | TORCNT_O 开向力矩次数(Torque Open Num.) | 0:No 1:Yes | |
1.2 | STARTCNT 启动次数(Start Num. Exceed) | 0:No 1:Yes | |
1.3 | ENDCNT_C 关向终端次数(End-Pos Close Exceed) | 0:No 1:Yes | |
1.4 | ENDCNT_O 开向终端次数(End-Pos Open Exceed) | 0:No 1:Yes | |
1.5 | RUNTIME 运行时间(Run Time Exceed) | 0:No 1:Yes | |
1.6 | Reserved | | |
1.7 | Reserved | | |
|
Fault Info | Byte0 | 0.0 | ELECTR 电子单元(Electric Unit) | 0:No 1:Yes | |
0.1 | PHASE 主电源缺相(Main Power Phase) | 0:No 1:Yes | |
0.2 | TEMP_MOT 电机温度(Motor Temp) | 0:No 1:Yes | |
0.3 | TEMP_ELC 电子温度(Electric Temp) | 0:No 1:Yes | |
0.4 | END_POS 超出终端(End Position) | 0:No 1:Yes | |
0.5 | RELAY 主继电器(Main Relay) | 0:No 1:Yes | |
0.6 | POS_LOSE 位置丢失(Position Lose) | 0:No 1:Yes | |
0.7 | Reserved | | |
|
Byte1 | | Reserved | | |
SetPointD | Byte | | 当前执行机构正在处理的开关量信号 | | |
SetPoint | Float | | 当前执行机构正在处理的调节量信号 | 0-100% | |