| | Z小 | | 标准 | | Z大 |
| 电源电压/输入电路(B1-B2/B3-B4) | | | |
| | | |
| 输入电压(B1-B2/B3-B4),标称电压 24 V DC | | 15 V | | 24 V | | 30V |
| 输出电流电路 > 25 V AC/60 V DC | | PELV,在B1-B2/B3-B4处 | |
| 输出电流电路 25 V AC/60 V DC | | SELV或PELV,在B1-B2/B3-B4上 | |
| 功耗(总功率) | | | 1.2 W | |
| 启动电流 | | | | 500 mA |
| 通电延迟(B1-B2/B3-4) | | | | 40 ms |
| 输出电流电路(13/14, 23/24, 33/34, 43/44, 51/52,Y1/Y2) | | |
| | | |
| 再激活延时 K1/K2 | | | 16 ms | | 20 ms |
| (保护功能的响应时间) | | | |
| 接点材料和表面处理 | | Ag合金;镀金 | | |
| 启用电流通路(常开触点),安全相关 | | 3 | | |
| 信号电流通路(常闭触点),非安全相关 | | 1 | | |
| | |
| 反馈电流通路(常闭触点,外部设备监控) | | 1 | | |
| | |
| | 积极引导 | | |
| 接触类型 | | |
| Z大接触荷载,反馈电流路径(Y1, Y2) | | | |
| 工作电压 直流 | | 10 V | | | 24 V |
| 开关电流 | | 5 mA | | | 100 mA |
| Z大接触负载 | | | |
| 启用电流通路(13, 14)(23, 24)(33,34)(43,44) | | | |
| 开关电压 AC | | 10 V | | | 230 V |
| 开关电压 DC | | 10 V | | | 300 V |
| 开关电流 | | 5 mA | | | 6:00 AM |
| Z大接触负载,信号电流通路(51,52) | | | |
| 开关电压 AC 4) | | 10 V | | | 230 V |
| 开关电压 DC | | 10 V | | 24 V | | 30 V |
| 开关电流 | | 5 mA | | | 2:00 AM |
| 总电流 | | | | 12:00 AM |
| 用途分类(EN 60 947-5-1) | | AC-15 Ue 230 V AC, Ie 4 A(360切换 |
| | 操作/小时) | | |
| | AC-15 Ue 230 V AC, Ie 3 A(3600切换 |
| | 操作/小时) | | |
| | DC-13 Ue 24 V DC, Ie 4 A(360切换 |
| | 操作/小时) | | |
| | DC-13 Ue 24 V DC, Ie 2.5 A(3600切换 |
| | 操作/小时) | | |
| 触点熔断保护 gG 或断路器(特点B或C) | | | | 6:00 AM |
| | |
| 允许开关频率 | | | | 3600/h |
| 机械使用寿命 | | 107开关操作 | |
| 运行数据 | | | |
| 防止身体接触的保护(EN 60 664 1、 | | | |
| EN 60 947 1) | | | |
| 额定脉冲电压VImp | | | 4 kV | |
| 过电压类别 | | | II4) | |
| 额定电压 | | | 300 V AC | |
| 测试电压 Urms 50 Hz | | | 2 kV | |
| 防护等级 | | | |
| 外壳 | | IP 40(EN 60 529) | | |
| 端子 | | IP 20(EN 60 529) | | |
| 安装 | | 安装轨(EN 60 715) | |
| 工作温度 | | –25 °C | | | +55 °C |
| 储存温度 | | –25 °C | | | +75 °C |
| 电线横截面积 | | | |
| | | | 2.5 mm² |
| 单线(1×) | | |
| 单线(2×,相同横截面积 | | 0.14 mm² | | | 0.75 mm² |
| 带套管的细绞线(1×) | | 0.25 mm² | | | 2.5 mm² |
| | | | 0.5 mm² |
| 带套管的细绞线(2× 相同横截面积) | | |
| 辐射发射 | | EN 61 000 6 4 | | |
| 抗干扰性 | | EN 61 000 6 2 | | |