中兴ZXDU68 T601电源系统是中兴通讯第四代电源Z有代表的产品。中兴ZXDU68 T601电源系统的电源柜采用三相四线制交流供电,整流器供电为单相220Vac,额定输出电流为50A;该组合电源系统有2m和1.6m两种标准机柜,由中兴ZXDU68 T601电源系统源柜的额定供电电流为600A,可以实现30A和50A整流器混插,方便维护。
中兴ZXDU68 T601(4.1)中兴室内电源参数及报价
中兴T601,中兴ZXDU68T601,中兴室内48v600A,中兴开关电源兴ZXDU68 T601电源系统是中兴通讯第四代电源Z有代表的产品。中兴ZXDU68 T601电源系统的电源柜采用三相四线制交流供电,整流器供电为单相220Vac,额定输出电流为50A;该组合电源系统有2m和1.6m两种标准机柜,由中兴ZXDU68 T601电源系统源柜的额定供电电流为600A,可以实现30A和50A整流器混插,方便维护。一、中兴ZXDU68 T601电源系统的监控单元无输入电源1.检查监控单元的电源输入端是否有电压2.检查监控单元的熔丝是否熔断3.检查监控单元的电源线插座是否插好二、屏幕显示混乱复位监控单元,如果仍不能解决该故障,需要取下监控单元进行检修三、与监控后台通讯中断1.检查波特率、设备地址、电话号码是否配置正确2.检查监控后台与监控单元SCB板的X16(RS232)之间的通讯电缆是否接好3.若采用Modem通讯方式,需要检查Modem的电缆和电源线是否连接好四、中兴ZXDU68 T601电源系统的整流器的状态检测和控制不正常1.若1~6号整流器的状态检测和控制不正常,请检查RSB板1是否插好2.若7~12号整流器的状态检测和控制不正常,请检查RSB板2是否插好五、交流数据或状态显示不正常检查监控单元SCB板的X3插头是否插接好六、直流数据或状态显示不正常检查监控单元SCB板的X17插头是否插接好七、电池温度检测不正常检查电池温度传感器与监控单元SCB板的X8,X9,X10之间的连线是否接好八、干接点输入检测不正常检测输入干接点与监控单元SCB板的X22之间的连线是否连接好九、中兴ZXDU68 T601电源系统的RLY板工作不正常检查RLY板与监控单元SCB板的X20之间的连线是否接好十、中兴ZXDU68 T601电源系统的监控单元指示灯不闪烁复位监控单元
ZTE/中兴 ZXDU68 T601 开关组合电源系统 现配300A 全新
**配置12个模块,600A,现配300A,量大从优,运费实出
ZXDU68 T601组合电源系统
随着运营商基站数量增加,其网络能耗迅速增长。站点获取也随着环保理念的深入人心而日益困难,土地租赁成本随之水涨船高。人力成本的日渐高涨,通信设备必须提高人机友好性以降低工程安装及日常维护费用。为满足用户全面降低TCO的要求,中兴通讯开发了ZXDU68
T601系列GX电源。
产品特点
一款GX率-48V室内组合电源系统,标准配置**33kW,并可根据用户需要单柜扩展至105kW。
包含更加丰富的外部接口:输入输出干接点、RJ45、RS232、RS485、USB,可以根据现场环境灵活组网。
系统采用效率高达96%的整流器,比传统电源更加节省能耗,减少CO2的排放。
功率密度更高,机柜深度400mm,前接线前维护设计,减少占地面积和维护空间。
监控单元采用彩色屏幕,视觉效果更好,同时使用人性化的九宫格设计,操作更加便利。
用户体验
高功率密度,节省占地空间高达50%,减少站点租赁费用支出80~300VAC宽输入电压范围,提升电池使用寿命-40~+70℃工作温度范围,野外适应能力更强,节省温控设备的费用采用GX率整流器,比传统电源节省电能高达10%监控单元通过USB接口,可以无限扩展监控的储存能力,并可实现快速开局ZTE ZXDU68 T601 power supply system is the most representative product of ZTE's fourth generation power supply. 1. Check whether the power input terminal of the monitoring unit has voltage 2. Check whether the fuse of the monitoring unit is fused 3. Check whether the power outlet of the monitoring unit is plugged in properly.
ZTE ZXDU68T601
1. ZTE ZXDU68 T601 power supply system without input power supply
1. Check whether the power input terminal of the monitoring unit has voltage 2. Check whether the fuse of the monitoring unit is fused 3. Check whether the power outlet of the monitoring unit is plugged in properly.
2. Screen display confusion
Reset the monitoring unit, if it still can't solve the problem, it needs to remove the monitoring unit for repair.
Interruption of communication with monitoring background
1. Check whether the baud rate, device address and telephone number are properly configured 2. Check whether the communication cables between the monitoring background and the SCB board X16 (RS232) are well connected 3. If modem communication mode is adopted, it is necessary to check whether modem cables and power cables are well connected.
4. Abnormal state detection and control of ZTE ZXDU68 T601 power supply system rectifier
1. If the state detection and control of No. 1-6 rectifier is abnormal, please check whether RSB board 1 is inserted properly. 2. If the state detection and control of No. 7-12 rectifier is abnormal, please check whether RSB board 2 is inserted properly.
5. Abnormal Display of Exchange Data or Status
Check whether the X3 plug of SCB board is plugged in properly
6. Abnormal display of DC data or status
Check whether the X17 plug of SCB board is plugged in properly
7. Abnormal Battery Temperature Detection
Check the connection between battery temperature sensor and SCB board X8, X9, X10
8. Improper input detection of dry contacts
Check whether the connection between input dry contacts and X22 of SCB board is well connected
9. The RLY board of ZTE ZXDU68 T601 power supply system is not working properly
Check whether the connection between RLY board and X20 board of SCB board of monitoring unit is good.
10. ZTE ZXDU68 T601 power supply system monitoring unit indicator does not flicker
Reset Monitoring Unit
ZTE ZXDU68T601
ZTE/ZTE ZXDU68 T601 switching combined power supply system is equipped with 300A brand-new genuine
** Configuration of 12 modules, 600A, 300A, large quantity, cost effective
ZXDU68 T601 Combined Power Supply System
With the increase of the number of base stations, the network energy consumption of operators increases rapidly. Site acquisition is becoming more and more difficult with the penetration of the concept of environmental protection, and the cost of land leasing is rising. With the increasing cost of manpower, communication equipment must improve man-machine friendliness in order to reduce the cost of engineering installation and daily maintenance. ZTE has developed ZXDU68 to meet the requirement of reducing TCO in an all-round way.
T601 Series High Efficiency Power Supply.
Product characteristics
A high efficiency - 48V indoor combined power supply system, standard configuration ** 33kW, and can be extended to 105kW single cabinet according to user needs.
Including more abundant external interfaces: input and output dry contacts, RJ45, RS232, RS485, USB, flexible networking according to the field environment.
The system uses a rectifier with efficiency up to 96%, which saves energy consumption and reduces CO2 emissions more than traditional power supply.
Higher power density, 400 mm cabinet depth, front wiring maintenance design, reduce occupied area and maintenance space.
The monitoring unit uses color screen, which has better visual effect. At the same time, it uses humanized Nine-palace design, which makes the operation more convenient.
User experience
High power density, saving space up to 50%, reducing site rental costs
80-300 VAC Wide Input Voltage Range to Enhance Battery Life
- Working temperature range of 40 ~+70 C makes field adaptability stronger and saves the cost of temperature control equipment.
Using high efficiency rectifier can save up to 10% energy than traditional power supply.
Through USB interface, the monitoring unit can expand the storage capacity of monitoring indefinitely, and achieve a fast start.