COMPLIANCE STANDARD | EN 60079-0, EN 60079-1, EN 60079-7, EN 60079-15, EN 61241-0, EN 61241-1 IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 61241-0, IEC 61241-1 & IEC 60529 |  |
CERTIFICATION | ATEX II 2 GD Ex d IIC / Ex e II / Ex tD A21 II 3 GD Ex nR II IECEx Ex d IIC / Ex e II / Ex tD A21 GOST-R Ex d IICU / Ex e IIU CSA Ex d IIC / Ex e II Class I Zone 1 Class I Division 2, Groups A, B, C & D Class II Division 2, Groups E, F & G Class III, Enclosure Types 3, 4 & 4X NEPSI Ex d IIC / Ex e II INMETRO BR - Ex d IIC / Ex e II / Ex nR II / Ex tD A21 ABS 1-1-4/7.7, 4.8-3/1.7, 4-8-3/13 and 4-8-4/27.5 MODU Rules 4-3-3/9 LLOYD’S Enclosure Systems (Part 1B) RMRS Part XI of Rules for sea-going ships (ed.2008) |
CERTIFICATE NO. | ATEX SIRA 01ATEX1271X SIRA 09ATEX1221X IECEx SIR 07.0097X GOST-R POCC GB.06.00853 CSA CSA 1356011 NEPSI GYJ06187X INMETRO NCC 5878/09 X ABS 09-LD463991-PDA LLOYD’S 10/00056 RMRS 09.00784.011 |
APPLICATION | EExd Equipment | E1WF type glands will only maintain Flameproof Exd integrity when used with cable that is substantially round and compact with extruded bedding. The cable shall be deemed to be effectively filled. Ref: IEC60079-14:2002 Section 10.4.2 | Gas Group | Internal Ignition Source | Enclosure Volume | Which Zone | Use E1WF Gland | IIC, IIB, IIA | NO | Any | Zone 1 or 2 | YES | IIB, IIA | YES | Any | Zone 2 | YES | IIB, IIA | YES | 2 litres or less | Zone 1 | YES | EExe Equipment | Other Equipment | Gas Group II, Zones 1 and 2 | Ignitable Dust, Zones 21 and 22 |
|
IP RATING | IP66 & IP68 (35 metres - 7 days), NEMA 4X |
MATERIALS | Brass CZ121 (E1WF) 316 Stainless Steel (E1WSF) Inner & outer sheath seal material: Standard (E1) Neoprene, black. Option (E3) Silicone, white. Reduced bore outer sheath seal (R) Silicone, red. (E1WFR). |
VARIATIONS | For lead sheath cables the gland is fitted with a metallic continuity washer: Brass (E2WF); 316 Stainless Steel (E2WSF). Integral Earth version for HV applications: Brass (E1WIEF); 316 Stainless Steel (E1WIESF) Omission of outer seal: Brass (D1WF); 316 Stainless Steel (D1WSF) |
OPTIONS | R | Reduced Bore Seal |
C | PVC Shroud (C) - PCP Shroud (P) - LSOH Shroud (3) |
K or V | Locknut, Earth Tag & Nylon (K) or Fibre (V) IP Washer |
S | Including Serrated Washer |
1 | Quantity per kit |
NP | Nickel Plated (NP) - Zinc Plated (ZP) |
OPERATING TEMPERATURES | Neoprene Seals -20ºC to +85ºC Silicone Seals -60ºC to +180ºC |
OPTIONAL ACCESSORIES | Locknut Brass (ACBLN) / Stainless Steel (ACSLN) Earth tag Brass (ACBET) / Stainless Steel (ACSET) IP Washers Nylon (ACNSW) / Fibre (ACFSW) Serrated Washer Stainless Steel (ACSSW) Shrouds PVC (ACSPVC) / PCP (ACSPCP) / LSOH (ACSSIO) |
EXAMPLE PART NUMBER | Sample: E1WBFCK1/NP/20/050NPT E Type of gland featuring armour specific clamping 1 Neoprene Seals (1) - Silicone (3) - Neoprene/Lead (2) - Silicone/Lead (4) W SWA (W) / SWB (X) or STA (Z) B Brass (B) / Stainless Steel (S) IE Integral Earth (see page TR-3) F Multiple Certification 20 Gland shell size 050NPT 1/2”NPT Entry Thread |
Gland Size | Entry Threads | Metric | NPT/BSP |
| Entry Thread Length [B] | Max Across Corners [A] | Max Protrusion Length | Gland Seal Range | Cable Inner Sheath [C] | Cable Outer Sheath [D] | Standard | Reduced (R) |
| Min | Max | Min | Max | Min | Max |
| Armour Acceptance Range | W | XZ |
| Shroud Size |
|
16 | M20 X 1.5 | 1/2" or 3/4" | 16 | 26.5 | 58.0 | 4.0 | 8.4 | 8.4 | 13.5 | 4.9 | 10.3 | 0.90 | 0.15- 0.35 | L24 | 20s | M20 X 1.5 | 1/2" or 3/4" | 16 | 26.5 | 58.0 | 8.0 | 11.7 | 12.9 | 16.0 | 9.4 | 12.5 | 0.90- 1.25 | 0.15- 0.35 | L24 | 20 | M20 X 1.5 | 1/2" or 3/4" | 16 | 33.0 | 58.0 | 6.7 | 14.0 | 15.5 | 21.1 | 12.0 | 17.6 | 0.90- 1.25 | 0.15- 0.50 | L30 | 25 | M25 X 1.5 | 3/4" or 1" | 16 | 41.4 | 58.0 | 13.0 | 20.0 | 20.3 | 27.4 | 16.8 | 23.9 | 1.25- 1.60 | 0.15- 0.50 | L38 | 32 | M32 X 1.5 | 1" or 1*1/4" | 16 | 50.6 | 65.0 | 19.0 | 26.3 | 26.7 | 34.0 | 23.2 | 30.5 | 1.60- 2.00 | 0.15- 0.55 | L46 | 40 | M40 X 1.5 | 1*1/4" or 1*1/2" | 16 | 60.5 | 72.0 | 25.0 | 32.2 | 33.0 | 40.6 | 28.6 | 36.2 | 1.60- 2.00 | 0.20- 0.60 | L55 | 50s | M50 x 1.5 | 1*1/2" or 2" | 16 | 71.5 | 73.0 | 31.5 | 38.2 | 39.4 | 46.7 | 34.8 | 42.4 | 2.00- 2.50 | 0.20- 0.60 | L65 | 50 | M50 x 1.5 | 2” | 16 | 71.5 | 73.0 | 36.5 | 44.1 | 45.7 | 53.2 | 41.1 | 48.5 | 2.00- 2.50 | 0.30- 0.80 | L65 | 63s | M63 x 1.5 | 2" or 2*1/2" | 19 | 88.0 | 76.0 | 42.5 | 50.1 | 52.1 | 59.5 | 47.5 | 54.8 | 2.50 | 0.30- 0.80 | L80 | 63 | M63 x 1.5 | 2*1/2" | 19 | 88.0 | 76.0 | 49.5 | 56.0 | 58.4 | 65.8 | 53.8 | 61.2 | 2.50 | 0.30- 0.80 | L80 | 75s | M75 x 1.5 | 2*1/2" or 3" | 19 | 99.0 | 82.0 | 54.5 | 62.0 | 64.8 | 72.2 | 60.2 | 68.0 | 2.50 | 0.30- 1.00 | L90 | 75 | M75 x 1.5 | 3” | 19 | 99.0 | 82.0 | 60.5 | 68.0 | 71.1 | 78.0 | 66.5 | 73.4 | 2.50 | 0.30- 1.00 | L90 | 80 | M80 x 2 | 3" or 3*1/2" | 25 | 115.2 | 110.0 | 62.2 | 72.0 | 77.0 | 84.0 | 71.9 | 79.4 | 3.15 | 0.45- 1.00 | L104 | 80H | M80 x 2 | 3" or 3*1/2" | 25 | 115.2 | 110.0 | 62.2 | 72.0 | 79.6 | 90.0 | 5.0 | 85.4 | 3.15 | 0.45- 1.00 | L104 | 85 | M85 x 2 | 3" or 3*1/2" | 25 | 115.2 | 110.0 | 69.0 | 78.0 | 79.6 | 90.0 | 75.0 | 85.4 | 3.15 | 0.45- 1.00 | L104 | 90 | M90 x 2 | 3*1/2" or 4" | 25 | 125.7 | 110.0 | 74.0 | 84.0 | 88.0 | 96.0 | 82.0 | 91.4 | 3.15 | 0.45- 1.00 | L114 | 90H | M90 x 2 | 3*1/2" or 4" | 25 | 125.7 | 110.0 | 74.0 | 84.0 | 92.0 | 102.0 | 87.4 | 97.4 | 3.15 | 0.45- 1.00 | L114 | 100 | M100 x 2 | 3*1/2" or 4" | 25 | 125.7 | 110.0 | 82.0 | 90.0 | 92.0 | 102.0 | 87.4 | 97.4 | 3.15 | 0.45- 1.00 | L114 | All Dimensions are in Millimetres | NOTES:- Gland size does not necessarily equate to the entry thread size. Gland size 16 is also available with an M16 x 1.5 entry thread.
- The IP O-ring seal option is only available on metric entry threads. IP washers can be supplied for tapered entry threads.
- Dimensions (A) & (B) may differ for glands with non metric entry threads. Please refer to our “Thread Reference Tables” for specific dimensions.
- Where glands are fitted into non-metallic Ex e enclosures they must be included within the earth circuit of the system.
- The user should seek expert advice if intending to combine flammable and combustible dust in one environment/installation.
- Assembly instructions must be read prior to installation and adhered to in full.
- Peppers supplies cable glands with parallel entry threads that conform to the flameproof threaded joint requirements of IEC/EN 60079-1 and other equivalent standards. They usually incorporate a thread run out according to the available machining techniques and will not have a full form thread for the entire length. Peppers will not be held responsible for clients’ installations where this has not been taken into account.
- To maintain the specified IP rating, clearance holes must be in accordance with EN 50262 Table 1 and the entry device should be suitably secured.
- For gland size 20 the silicone inner seal has a minimum diameter of 11.0mm and NOT 6.7mm
- All gland kits supplied with silicone seals will include a PTFE IP washer in order to maintain the temperature range.
|
|